Przejdź do treści
Liczbnik

Heating Power Calculator — How Many kW to Heat a House

The heating power calculator helps you make a first estimate of the heat output (in kW) needed to heat a building. Enter the heated floor area, choose the insulation standard and ceiling height — the calculator returns the power demand, the W/m² index and a recommended boiler or heat pump power with a margin. This is a simplified rule of thumb, useful at the planning stage.

Reviewed byRedakcja Liczbnik
Calculator
m²
m
Required heating powerHeating power (kW)8
Demand (W/m²)
80
Recommended boiler power (kW)
9

How the calculator estimates heating power

W/m² index by building standard: Low (well insulated, WT2021) = 50 W/m² Medium (standard) = 80 W/m² High (old, poorly insulated) = 120 W/m² Power (W) = area × index × (height / 2.7) Power (kW) = power (W) / 1000 Recommended boiler power = power × 1.1, rounded up to 0.5 kW

Example: 100 m², standard insulation, 2.7 m height

A 100 m² house, standard insulation (80 W/m²), 2.7 m height: power = 100 × 80 × (2.7/2.7) = 8000 W = 8.0 kW. Recommended boiler power with a 10% margin = 8.0 × 1.1 = 8.8

rounded up to 9.0 kW.

Frequently asked questions

How many kW of heating power per square metre?

Rule-of-thumb indices are: well-insulated houses (new, WT2021) about 40–60 W/m², standard buildings about 70–90 W/m², and old, poorly insulated ones about 100–130 W/m². The calculator uses 50, 80 and 120 W/m². For a 100 m² house with standard insulation that is about 8 kW.

What does the building standard mean in the calculator?

The standard reflects approximate energy demand. "Low" (50 W/m²) means well-insulated buildings or those meeting WT2021. "Medium" (80 W/m²) is a typical house from 2000–2015. "High" (120 W/m²) means old buildings from before the 1990s, uninsulated or with large heat losses.

What is the WT2021 standard?

WT2021 is the Polish technical requirement in force since 2021, setting the maximum building energy demand and minimum insulation parameters of the envelope. Houses built to WT2021 have low heat losses and fall into the "low" demand class (about 50 W/m² or less).

Does ceiling height affect heating power?

Yes. We heat volume, not just floor area. Taller rooms have a larger air volume and bigger walls through which heat escapes. The calculator scales power proportionally to height relative to a 2.7 m baseline — at 3.0 m the power rises by about 11%.

Why should you avoid oversizing the boiler?

An oversized boiler runs in constant on/off cycling (short-cycling), which lowers efficiency, increases fuel use and accelerates wear. That is why power is chosen close to the real demand, adding only a small margin — about 10% in this calculator.

How is heat pump power sized?

Heat pumps must be sized especially precisely, because oversizing worsens efficiency (COP/SCOP) and causes compressor short-cycling. Power is chosen so the pump covers most of the season, with a heating element assisting in extreme cold. Here an OZC calculation is especially recommended over the rule of thumb.

Indicative result

Results are indicative and based on a simplified rule of thumb (W/m²). They do not account for the actual insulation of the building envelope, ventilation, solar gains or climate zone. For sizing a boiler or heat pump, a proper heat-loss (OZC) calculation by a designer or installer is recommended.
See all